9300 Servo PLC
System blocks
2.2 Automation interface (AIF1_IO_AutomationInterface)
2-6
9300ServoPLC EN 1.4
VariableName NoteDIS formatDISAddressSignalTypeDataType
AIF1_bInB16_b Bool binary %IX41.3.0 C0855/2 hex
AIF1_bInB17_b Bool binary %IX41.3.1 C0855/2 hex
AIF1_bInB18_b Bool binary %IX41.3.2 C0855/2 hex
AIF1_bInB19_b Bool binary %IX41.3.3 C0855/2 hex
AIF1_bInB20_b Bool binary %IX41.3.4 C0855/2 hex
AIF1_bInB21_b Bool binary %IX41.3.5 C0855/2 hex
AIF1_bInB22_b Bool binary %IX41.3.6 C0855/2 hex
AIF1_bInB23_b Bool binary %IX41.3.7 C0855/2 hex
AIF1_bInB24_b Bool binary %IX41.3.8 C0855/2 hex
AIF1_bInB25_b Bool binary %IX41.3.9 C0855/2 hex
AIF1_bInB26_b Bool binary %IX41.3.10 C0855/2 hex
AIF1_bInB27_b Bool binary %IX41.3.11 C0855/2 hex
AIF1_bInB28_b Bool binary %IX41.3.12 C0855/2 hex
AIF1_bInB29_b Bool binary %IX41.3.13 C0855/2 hex
AIF1_bInB30_b Bool binary %IX41.3.14 C0855/2 hex
AIF1_bInB31_b Bool binary %IX41.3.15 C0855/2 hex
AIF1_dnInD1_p Double integer position %ID41.1 C0857 dec [inc] 65536 = 1 revolution
Function
Theinputsignalsofthe8byteuserdataoftheAIF-objectareconvertedintocorrespondingsignal
types.
Byte 1 and 2
Byte 1,2 can be used simultaneously as
• binary information (up to 16 bits),
• as word (e.g. as control word)
Bytes 3 and 4
Bytes 3-4 form the signal for
AIF1_nInW1_a
.
Bytes 5-6 and bytes 7-8
The meaning of these user data can be selected among different signal types. Depending on the
requirement, thesedata can be evaluated as up to 2 integer signals, 32 boolean/digital signals or one
double-integer signal.
Address range from byte 1 - 7
Byte Address
1, 2 %IB41.0 and %IB41.1
3, 4 %IB41.2 and %IB41.3
5, 6 %IB41.4 and %IB41.5
7, 8 %IB41.6 and %IB41.7