9300 Servo PLC
System blocks
2.6 Analog inputs/outputs 1 (ANALOG1_IO)
2-22
9300ServoPLC EN 1.4
2.6.2 Outputs_ANALOG1 (AOUT1)
Analog output 1 (module number: 11)
You can use this SB as a monitor output. Internal analog signals can be output via terminal X6/62 as
voltage signals, and used, for example, as display or setpoints for following drives.
62
X6
AOUT1
AOUT1_nOut_a
C0434/1
Abb. 2-12 Outputs_ANALOG1 (AOUT1)
VariableName
DataType SignalType Address DIS DIS format Note
AOUT1_nOut_a Integer analog %QW11.0 C0434/1 dec [%] Analog output 1
Function
• A voltage of 10 V is given out at terminal X6/62, if the signal on
AOUT1_nOut_a
= 16384 =
100 %
• Processing time required for the SB: 12 µsec.
Assignment of the control terminal X6/62
Termin al Use level Data
X6/62 Monitor 1 -10Vto+10V;
max. 2 mA
Resolution:
20 mV (9 bit + sign)
±10 V ≡±16384 ≡±100 %
X6/7 Internal ground, GND - -