9300 Servo PLC
System blocks
2.7 Analog inputs/outputs 2 (ANALOG2_IO)
2-24
9300ServoPLC EN 1.4
2.7.2 Outputs_ANALOG2 (AOUT2)
Analog output 2 (module number: 12)
You can use this SB as a monitor output. Internal analog signals can be output via terminal X6/63 as
voltage signals, and used, for example, as display or setpoints for following drives.
C0439/1
63
AOUT2
AOUT2_nOut_a
X6
Abb. 2-14 Outputs_ANALOG2 (AOUT2)
VariableName
DataType SignalType Address DIS DIS format Note
AOUT2_nOut_a Integer analog %QW12.0 C0439/1 dec [%] Analog output 2
A voltage of 10 V is given out at terminal X6/63, if the signal on
AOUT2_nOut_a
= 16384 =
100 %
Processing time required for the SB: 12 µsec.
Assignment of the control terminal X6/63
Termin al Use level Data
X6/63 Monitor 2 -10Vto+10V;
max. 2 mA
Resolution:
20 mV (9 bit + sign)
±10 V ≡±16384 ≡±100 %
X6/7 Internal ground, GND - -