3.1.2 Wiring of the system bus
Basic structure shown at a Drive PLC with 8200 vector
plc014
Drive PLC Controller 1 Controller 2
GND LOW HI GG LO HI GG LO HI GG LO HI GG LO
120
120
HI
PES PES
Abb. 3-1 Basic structure of a system bus network
Comments on wiring
We recommend the following signal cable for the wiring:
Specification system bus cable Totallengthupto300m Total length up to 1000 m
Cable type LIYCY2x2x0.5mm
2
(twisted pairs, with screening)
CYPIMF2x2x0.5mm
2
(twisted pairs, with screening)
Cable resistance 40 /km 40 /km
Capacitance per unit length 130 nF/km 60 nF/km
Connection Pair 1 (white/brown): LO and HI
Pair 2 (green/yellow): GND
Tab. 3-1 Specification of the system bus cable
Tip!
A terminating resistor of R = 120 must be connected to the first and last physically
connected device (see Abb. 3-1).
Connect cable screen over a large surface to PE potential (PES).