9300 Servo PLC
System blocks
2.11 Digital inputs/outputs (DIGITAL_IO)
2-44
9300ServoPLC EN 1.4
2.11.2 Outputs_DIGITAL (DIGOUT)
Digital outputs (module number: 1)
This SB conditions the digital signals, and outputs them at terminals X5/A1 ... X5/A4.
A1
A2
A3
A4
1
0
C0118/1...4
DIGOUT
C0444/4
C0444/3
C0444/2
C0444/1
X5
1
DIGOUT_bOut1_b
DIGOUT_bOut2_b
DIGOUT_bOut3_b
DIGOUT_bOut4_b
Abb. 2-26 Outputs_DIGITAL (DIGOUT)
VariableName
DataType SignalType Address DIS DIS format Note
DIGOUT_bOut1_b Bool binary %QX1.0.0 C0444/1 bin
DIGOUT_bOut2_b Bool binary %QX1.0.1 C0444/2 bin
DIGOUT_bOut3_b Bool binary %QX1.0.2 C0444/3 bin
DIGOUT_bOut4_b Bool binary %QX1.0.3 C0444/4 bin
Function
• Electrical data of the output terminals:
Termin al Use (Lenze setting in bold print) Data
X5/A1 freely assignable
LOW: 0 0 +4 V
X5/A2 freely assignable
HIGH: + 13 0 + 30 V
X5/A3 freely assignable
X5/A4 freely assignable
utput cu
ent:
X5/39 Ground of the digital inputs and outputs
.
u
u
e
te
nal
esistance at least 480 Ω at 24
X5/59 Supply input for the control module:
24 V external (I > 1A)
• Delay times:
–For
DIGOUT_bOut1_b
...
DIGOUT_bOut4_b
it lies in the range from 100 µs ... >300 µsec.
• The level for every output can be inverted. For this, proceed as follows:
– Select code C0118 with corresponding subcode (e.g. subcode 3 for output X5/A3)
– Enter the desired level as a parameter:
0 = level not inverted (HIGH active)
1 = level inverted (LOW active)