2.7 Analog inputs/outputs 2 (ANALOG2_IO)
2-23
9300ServoPLC EN 1.4
2.7 Analog inputs/outputs 2 (ANALOG2_IO)
2.7.1 Inputs_ANALOG2 (AIN2)
Analog input 2 (module number 12)
This SB forms the interface for analog signals via terminal X6/3-4.
3
4
AIN2
AIN 2_nIn_a
X6
C0405
Abb. 2-13 Inputs_ ANALOG2 ( AIN2)
VariableName
DataType SignalType Address DIS DIS format Note
AIN2_nIn_a Integer analog %IW12.0 C0405 dec [%] Analog input 2
• Processing time required for the SB: 10 µsec.
Asssignment of the control terminals X6/3-4
Termin al Use level Data
X6/3
X6/4
Differential master-voltage input
(jumper X3 has no effect)
-10 Vbis +10 V Resolution:
5 mV (11 bit + sign)
±10 V ≡±16384 ≡±100 %