EasyManua.ls Logo

Lenze 9300 Servo PLC - 2.13.12 System marker MCTRL_nNmaxC11; 2.13.13 Monitoring; 2.13.13.1 Undervoltage (LU)

Lenze 9300 Servo PLC
175 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9300 Servo PLC
System blocks
2.13 Internal motor control (MCTRL_MotorControl)
2-57
9300ServoPLC EN 1.4
Example (
MCTRL_nNAct_v
in a 10 msec task):
When the 10 msec task starts, the value of the counter is stored in a local area of the task and
the counter is reset. The value in the local area gives an average value in increments per 1
msec.
If a position value is to be derived from this value, then it must be multiplied by
SYSTEM_nTaskInterval
/ 4, to get the result in increments per 10 msec, as in the example.
Example: In a 1 msec task,
SYSTEM_nTaskInterval
has the value 4 (4 * 250 µs=1msec)
For Lenze FBs, this procedure has already been implemented in the FBs.
2.13.12 System marker MCTRL_nNmaxC11
The system marker
MCTRL_nNmaxC11
shows the max. speed set under C0011. This value is the
reference value for all _a” values (16384
MCTRL_nNmaxC11
)
With the help of this system marker you can program your own scaling routines in the
parameter manager.
Example: C0011 = 3000 rpm
MCTRL_nNmaxC11
= 3000
2.13.13 Monitoring
Various monitoring functions protect the drive from impermissible operating conditions.
If a monitoring function is activated,
the corresponding set reaction is triggered,
boolean (logic) variables are set to TRUE. You can use these variables in the PLC application
program.
2.13.13.1Undervoltage(LU)
This function monitors the DC-bus and protects the drive.
The message is triggered by
MCTRL_bUndervoltage_b
=TRUE.
Supply voltage range Selection number
(C0173)
Switch-off threshold Switch-on threshold
< 400 V 0 285 V 430 V
400 V 1 285 V 430 V
400 0 460 V 2 328 V 473 V
480 V without brake chopper 3 342 V 487 V
Operation with brake chopper
(up to 480 V)
4 342 V 487 V
Function
The monitoring reacts if the DC-bus voltage (terminal +U
G
and -U
G
) goes below the threshold
(switch-off level)that was set by C0173.
The message is reset if the voltage goes above the switch-off threshold again.
Theswitch-off threshold determinesthe voltagelevel of theDC-bus voltageat whichthepulseinhibit
is activated.
The input variable
MCTRL_bUndervoltage_b
canbeprocessedinthePLCapplicationprogram.
The selection number is also effective for the overvoltage monitoring OU.
(
^
2-58)
Adapt the setting of the codes to the available mains voltage (also for operation
via+U
G
/-U
G
-terminals). When the controller is operated in a network of drives, all controllers must
have the same setting.
Show/Hide Bookmarks

Table of Contents

Related product manuals