9300 Servo PLC
System blocks
2.10 Digital frequency output (DF_OUT_DigitalFrequency)
2-40
9300ServoPLC EN 1.4
2.10.2 Output of an analog signal
Selection: C0540 = 0
The input signal
DFOUT_nOut_v
is interpreted as an analog signal [%] and given out as a frequency
signal at the master frequency output X10.
• 100 % ≡ (INT)16384 ≡ C0011 (n
max)
Transmission function
f[Hz] DFOUT_nOut_v [%] ô
no. of incr._from C0030
100
ô
C0011 (n
max
)
60
Example:
•
DFOUT_nOut_v
=50%
• C0030 = 3, this corresponds to 2048 inc/rev.
• C0011 = 3000 rpm
f[Hz] 50 % ô
2048
100
ô
3000
60
51200 Hz
2.10.3 Output of a speed signal
Selection: C0540 = 1
The input signal
DFOUT_nOut_v
is interpreted as a speed (rpm) signal [%] and given out as a
frequency signal at X10.
• 15000 rpm ≡ (INT)16384
Transmission function
f[Hz] DFOUT_nOut_v [rpm] ô
no. of incr._from C0030
60
Example:
•
DFOUT_nOut_v
= 3000 rpm
• C0030 = 3, this corresponds to 2048 inc/rev.
f[Hz] 3000 rpm ô
2048
60
102400 Hz
2.10.4 Encoder simulation of the resolver with zero track in resolver zero position
Selection: C0540 = 2
• The function is used if a resolver is connected to X7.
• The encoder constant for output X10 is set under C0030.
• The output of the zero pulse referring to the motor depends on how the resolver is attached to
the motor.
– The zero pulse can be shifted by +360° under C0545 (65536 inc = 360°).