EasyManua.ls Logo

Lenze 9300 vector Series - Page 176

Lenze 9300 vector Series
330 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical installation
Standard devices in the power range 0.37 ... 11 kW
Motor connection
5
176
EDKVF9333V DE/EN/FR 7.2
PE PE
UUVVWW
T1 T1T2 T2
U, V, W
T1, T2
0.5...0.6 Nm
4.4...5.3 lb-in
U, V, W
T1, T2
0.5...0.6 Nm
4.4...5.3 lb-in

2233
1
1
00
9300std011
Fig. 5−6 Motor connection with PTC thermistor or thermal contact (NC contact)
Motor connection with Lenze system cable with integrated control cable for the motor
temperature monitoring
Shield sheet
Clamp entire shield and shield of the control cable for the motor temperature monitoring
with the straps. If required, fix by means of cable tie.
Motor cable connection and separate control cable for the motor temperature monitoring
Shield sheet
Clamp shield of the motor cable and shield of the cable for the motor temperature
monitoring with the straps. If required, fix by means of cable tie.
U, V, W
Motor cable connection
Check the correct polarity. Observe maximum length of the motor cable. Use wire end ferrules
for flexible cables.
Max. connectable cable cross−section: 4 mm
2
, with pin−end connector > 4 mm
2
T1, T2 for motor temperature monitoring
Cable connection for PTC thermistors or thermal contacts (NC contacts)

Table of Contents

Other manuals for Lenze 9300 vector Series

Related product manuals