Installation Manual Liebert Hipulse E Chapter 5 – ‘Specification’
Single or '1+N' UPS System
(07/04) Page 5-1
5 Chapter 5 - Specification
This specification describe requirements for an Uninterruptible Power System (UPS).
5.1 Conformity and Standard
The UPS has been designed to conform to the following standards:
Description Year Normative references
General and safety requirements for
UPS used in operator access areas
2002
EN 62040-1-1
IEC 62040-1-1
Emissions requirements 1995
EN 50091-2 (tables 2 and 4)*
Method of specifying the performance
and test requirements
2001
EN 62040-3 identical to
IEC 62040-3 (1999)
* Class ‘A’ compliance if optional RFI filters is fitted (only for 300 kVA UPS)
C
C
E
E marked
The above mentioned product standards incorporate relevant compliance clauses with generic IEC and EN standards
for safety (60950) and construction (60529).
For more details, see below:
Description Year Normative references
Information technology equipment 2000 EN 60950
Degrees of protection provided by
enclosures (IP code).
1989 EN 60529
5.2 UPS Environmental
The UPS shall be able to operate under the following environmental conditions without damage or degradation in
electrical operating characteristics:
ENVIRONMENTAL
CHARACTERISTICS
UNITS
Rated power kVA 300 400
Operating Temperature °C 0- 40
Maximal temperature for 8 hr day °C
40°C
de-rate power by 1,5% per °C between +40°C and + 50°C
Mean Temperature for 24 h °C 35
Relative humidity
90% at 20°C
Acoustical noise dBA 70 73
Altitude of operation
1000m asl
de-rate power by 1% per 100m between 1000 and 2000 m
Storage-Transport Temperature °C
-25 ÷ 70