L-DALI User Manual 347 LOYTEC
Version 5.2 LOYTEC electronics GmbH
Present_Value (Read-Only)
This property, of type REAL, indicates the linearized percentage (0..100.00%) of the
constant light controller output.
Description (Read/Write)
This property can be configured via BACnet. It serves documentation purposes only.
Reliability (Read-Only)
The Reliability property for this object type may have any of the following values:
NO_FAULT_DETECTED No fault was detected.
OPEN_LOOP The sensor value does not change when the output is
controlled (CONTROL mode only).
COMMUNICATION_FAILURE Communication with sensor or light output not working.
UNRELIABLE_OTHER Other failure detected.
Output_Units (Read-Only)
The value of this property is 98 (percent).
Manipulated_Variable_Reference (Read/Write)
Specifies the object and property the value of the Present_Value property is written to.
Controlled_Variable_Reference (Read/Write)
Specifies the object and property the light sensor value is read from.
Controlled_Variable_Value (Read/Write)
This property holds the current light sensor value as read from
Controlled_Variable_Reference.
Controlled_Variable_Units (Read-Only)
The value of this property is 37 (lux).
Setpoint_Reference (Read/Write)
Specifies the object and property the setpoint for the constant light controller algorithm is
read from.
Setpoint (Read/Write)
This property holds the setpoint for the constant light controller algorithm.
Action (Read-Only)
The value of this property is DIRECT.
Profile_Name (Read-only)
The value of this property is “178-http://www.loytec.com/xsd/ConstantLightController/v1”.