L-DALI User Manual 86 LOYTEC
Version 5.2 LOYTEC electronics GmbH
Function
Description
Disabled
No action
Generic
Button input status will be reflected by the assigned LONMARK
network variable (see Section 8.2.11) or BACnet object if
available (see Section 8.3.6).
On (maximum)
Switch on (recall maximum).
On (last value)
Switch on to last known value.
Note: Requires storing value when switching off.
Off
Switch off.
Off (store value)
Store last value and switch off.
On/Off
Toggle between on and off whenever button is pressed or
switch is changed depending on current status (changeover
switch). Switch light on when it is off and switch light off
when it is on.
Up
Dim up while button is pressed. The dim speed is determined
by the parameter nciFadeRate (LONMARK) and Ramp_Rate
(BACnet) of the affected ballasts.
Down
Dim up while button is pressed. The dim speed is determined
by the parameter nciFadeRate (LONMARK) and Ramp_Rate
(BACnet) of the affected ballasts.
Up/Down
Toggle between dimming up and down whenever button is
pressed. Dim as long as button is kept pressed. The dim speed
is determined by the parameter nciFadeRate (LONMARK) and
Ramp_Rate (BACnet) of the affected ballasts.
On/Up
Switch on (recall maximum) if button is pressed shortly, dim
up when button kept pressed. The dim speed is determined by
the parameter nciFadeRate (LONMARK) and Ramp_Rate
(BACnet) of the affected ballasts.
On (last value)/Up
Switch on to last known value if button is pressed shortly, dim
up when button kept pressed. The dim speed is determined by
the parameter nciFadeRate (LONMARK) and Ramp_Rate
(BACnet) of the affected ballasts.
Off/Down
Switch off value if button is pressed shortly, dim down when
button kept pressed. The dim speed is determined by the
parameter nciFadeRate (LONMARK) and Ramp_Rate (BACnet)
of the affected ballasts.
Off (store value/Down)
Store last value and switch off if button is pressed shortly, dim
down when button kept pressed. The dim speed is determined
by the parameter nciFadeRate (LONMARK) and Ramp_Rate
(BACnet) of the affected ballasts.
On/Off and Up/Down
Toggle between on and off whenever button is pressed shortly
depending on current status (changeover switch). Toggle
between dimming up and down whenever button is pressed
longer. Dim as long as button is kept pressed. The dim speed is
determined by the parameter nciFadeRate (LONMARK) and
Ramp_Rate (BACnet) of the affected ballasts.
On (last value)/Off and
Up/Down
Toggle between switching on to last value and off (including
storing the last value) whenever button is pressed shortly
depending on current status (changeover switch). Toggle
between dimming up and down whenever button is pressed
longer. Dim as long as button is kept pressed. The dim speed is
determined by the parameter nciFadeRate (LONMARK) and
Ramp_Rate (BACnet) of the affected ballasts.
Dim to
Dim to the value entered as argument 1.
Dim to (toggle)
Toggle between dim value entered as argument 1 and dim
value entered as argument 2 whenever button is pressed or

Table of Contents