Application Manual CDA3000
5-39
5 Software functions
1
2
3
4
5
6
A
DE
EN
FR
Figure 5.13 Wiring for reference coupling via clock signal 0-10 kHz
Note: The clock cables must be shielded. The shield must be
grounded over a wide area on one side.
Explanatory notes
By way of the digital input ISD01 the reference of the device can
be specified with a clock signal of 0-10 kHz. The function selector
211-FIS01 must be set to INCLK.
A clock signal proportional to the output frequency of the device can
be delivered at OSD01. The transmission ratio is adjustable in
increments of 2
n
from 1x to 128x, and is limited to the switching
frequency of the power stage (parameter 690-PMFS). The function
selector 241-FOS01 must be set to OCLK.
Function Des. X2
Digital ground DGND 17
Clock output OSD01 18
FunctionDes.X2
Digital ground
Clock input
DGND
ISD01
17
10