5-90
Application Manual CDA3000
5 Software functions
5.4 Bus operation
and option
modules
This Manual details only the software parameters of the CDA3000 inver-
ter module. For more details on the field bus systems refer to the relevant
documents relating to the option modules.
5.4.1 _55 LB-LUSTBUS
Parameters for LUSTBUS
Function Effect
Creation of the device
addresses and baud rate for
the service and diagnostic
interface
Adaptation of the serial inter-
face (RS232) to as PC with
the D
RIVEMANAGER software
or the K
EYPAD KP200
Parameter Function Value range FS Unit Online
81-SBAUD LUSTBUS transfer rate
9600
1200
2400
4800
19200
2880
57600
57600 Bit/s
82-SADDR LUSTBUS device address 0 ... 30 1
83-SDMMY LUSTBUS dummy parameter 0 ... 255 0
84-SWDGT LUSTBUS watchdog time setting 0.00 ... 20.00 0.00 s
85-SERR LUSTBUS error status word 00H ... FFH 00 Hex
550-SSTAT Status word of serial interface 0 ... 65535 0
551-SCNTL Control word of serial interface 0000H ... FFFFH 0000Hex
Table 5.52 Parameters from subject area _55LB LUSTBUS
Explanatory notes
If only one inverter module is operated on the DRIVEMANAGER no
device address need be set. For more than one device, different
address parameters must be set.
The L
USTBUS watchdog time setting is deactivated to 0.0 s at the
factory.