Application Manual CDA3000
4-61
4 Application data sets
1
2
3
4
5
6
A
DE
EN
FR
4.6.5 Comparison of
parameters,
Master/-Slave
operation
Comparison of the application data sets for Master/-Slave operation
with the factory setting (152-ASTER = DRV_1):
I/O Parameter Function
152-ASTER =
DRV_1
(FS)
M-S_1 M-S_2 M-S_3 M-S_4
Initial commissioning
151-ASTPR Original device preset DRV_1 M-S_1 M-S_2 M-S_3 M-S_4
152-ASTER Preset within the active application data set DRV_1 M-S_1 M-S_2 M-S_3 M-S_4
166-UDSSL
Control location for switchover of the active user
data set
PARAM 1) 1) 1) 1)
300-CFCON Current open-loop/closed-loop control mode of the VFC FOR FOR
CDA3000 inverter module inputs and outputs
ISA00 180-FISA0 Function selector analog standard input ISA00 OFF PM10V PM10V
ISD01 211-FIS00 Function selector digital standard input ISD01 STL FSMI FSMI
ISD02 212-FIS02 Function selector digital standard input ISD02 SADD1 MP-UP ENC MP-UP ENC
ISD03 213-FIS03 Function selector digital standard input ISD03 OFF MP-DN ENC MP-DN ENC
OSA0 200-FOSA0 Function selector for analog output OSA00 AACTF
OSD0 240-FOS00 Function selector digital standard output OSD00 BRK_1 ROT_0 ROT_0 ROT_0 ROT_0
OSD0 241-FOS01 Function selector digital standard output OSD01 REF FMSO FMSO OFF OFF
OSD0 242-FOS02 Function selector digital standard output OSD02 S_RDY
Reference structure
280-RSSL1 Reference selector 1 FMAX FA0 FA0 FDIG FDIG
281-RSSL2 Reference selector 2 FCON
289-SADD1 Offset for reference selector 1 10 0 0 0
MOP function
320-MPSEL Configuration for motor operated potentiometer OFF F1 F1
Driving profile generator
597-RF0 Response at reference value 0 Hz OFF 0 Hz 0 Hz
Current-controlled startup
640-CLSL1 DS1: Function selector CCWFS CCWFR OFF CCWFR OFF
645-CLSL2 DS2: Function selector CCWFS CCWFR OFF CCWFR OFF
DC holding
681-HODCT Holding time 0.5 0 0
1) After setting the parameters of the user data sets, change parameter value 166-UDSSL from PARAM (KEYPAD KP200,
D
RIVEMANAGER) to TERM (terminal operation).
Table 4.27 Automatic changes by means of the assistance parameter
An empty line means that the setting is the same as for DRV_1 (factory set-
ting).