6-56
Application Manual CDA3000
6 Control modes
6.3.3 _80 CC-Current
control
Note: The parameters of the current control subject area are
detailed in section 5.5.10. Please note the information given
there.
Parameters of current control
Function Effect
Setting of current controller
functions
Optimum parameter setting
of the PI current controller
Parameter Function Value range FS Unit Online
800-CCG Current controller gain 0...500 48
801-CCTLG Current controller lag time 0.001...100 0.0036 s
802-CCTF Filter time constant for current measurement in SFC 0.0005...20 0.01 s
803-VCSFC Correction factor of fault voltage characteristic 0...199 70 %
804-CLIM1 CDS1: Maximum reference current for current control 0...180 100 %
805-CLIM2 CDS2: Maximum reference current for current control 0...180 100 %
Table 6.29 Parameters of subject area _80CC Current control
Explanatory notes
No adaptation of the fault voltage compensation is required.
The parameters of the current controller are set automatically during
auto-tuning in initial commissioning. It is not necessary to change
the calculated values of the PI controller for the gain (800-CCG) or
the lag time (801-CCTLG).