6-36
Application Manual CDA3000
6 Control modes
6.2.3 Tips and optimi-
zation aids
for control
engineers
The following presents a systematic procedure for setting of the control.
Note: In the event of strong load surges resulting in rapid speed
changes, the stator flux orientation of the SFC may be lost,
and current overload shut-offs (error E-OC) may occur. This
error is counteracted by the current-controlled startup func-
tion (see section 5.5.11) setting a steep lowering ramp.
Step Checks Help
1
Check that your wiring is connected properly
and the phase sequence is correct.
see section 2.1 Device and terminal
view.
2
Enter correct (plausible) motor data and start
auto-tuning.
see section 5.1 _15 FC-Initial com-
missioning.
3 Check the fault voltage compensation.
Optimization of the D-current in this
section
4
Check the limit values for the apparent
current.
Setting of the current limitation in
this section
5 Check the speed controller.
Optimization of the speed controller
in this section
Table 6.15 Procedure for optimization of SFC