5-4
Application Manual CDA3000
5  Software functions
5.1 _15 FC-Initial 
commissioning
The general procedure for initial commissioning is described in the oper-
ating instructions and in section 3.5.
Initial commissioning parameters
Function Application
• Input of the characteristic motor data
• Selection and activation of the appli-
cation data set with the preset solu-
tions
• Controller auto-tuning
• Quick and easy commissioning of 
the inverter module
• Automatic setup of all controllers
• Identification of the connected motor
Parameter Function Value range FS Unit Online
150-SAVE Back-up device setup STOP/START
151-ASTPR Original device preset DRV_1 ... M-S_4 DRV_1
152-ASTER Preset (ADS)
OFF ... M-S_4
see 4.1
DRV_1
154-MOPNM Motor rated power * * kW
155-MOVNM Motor rated voltage * * V
156-MOFN Motor rated frequency 0.1 ... 1000 50 Hz
157-MOSNM Rated speed 0 ... 100000 * rpm
158-MOCNM Motor rated current * * A
159-MOCOS Motor cosϕ 0 ... 1 1
160-MOJNM Mass moment of inertia of the motor 0 ... 100
see Table 
5.4
161-SCJ1
CDS1: Mass moment of inertia of the 
system 
0 ... 1000 0
162-SCJ2
CDS2: Mass moment of inertia of the 
system
0 ... 1000 0
163-ENSC Enable auto-tuning STOP/START STOP
164-UDSWR Back-up device setup in a user data set 1 ... 4 1
165-UDSAC Activate user data set 1 ... 4 1
166-UDSSL
Control location for switchover of the 
active user data set 
see Table 5.14 PARAM
167-SCPRO Auto-tuning progress indicator 0 ... 100 0 %
300-CFCON
Current open-loop/closed-loop control 
mode of the device
see Table 5.9 VFC
Table 5.1 Parameters of subject area “_15 FC-Initial commissioning”