Application Manual CDA3000
4-47
4  Application data sets
1
2
3
4
5
6
A
DE
EN
FR
4.5.4 Comparison of 
parameters, 
field bus 
operation
Comparison of the application data sets for field bus operation with the
factory setting (152-ASTER = DRV_1):
I/O Parameter Function
152-ASTER =
DRV_1
(FS)
BUS_1 BUS_2 BUS_3
Initial commissioning
151-ASTPR Original device preset DRV_1 BUS_1 BUS_2 BUS_3
152-ASTER Preset within the active application data set DRV_1 BUS_1 BUS_2 BUS_3
166-UDSSL
Control location for switchover of the active user data 
set
PARAM 1) 1) 1)
CDA3000 inverter module inputs and outputs
ISA00 180-FISA0 Function selector analog standard input ISA00 OFF OPTN2 PM10V PM10V
ISA01 181-FISA1 Function selector analog standard input ISA01 OFF OPTN2 MAN
ISD00 210-FIS00 Function selector digital standard input ISD00 STR OPTN2
ISD01 211-FIS01 Function selector digital standard input ISD01 STL OPTN2
ISD02 212-FIS02 Function selector digital standard input ISD02 SADD1 OPTN2 MAN /LCW
ISD03 213-FIS03 Function selector digital standard input ISD03 OFF OPTN2 OPTN2 /LCCW
OSA00 200-FOSA0 Function selector for analog output OSA00 AACTF OFF
OSD00 240-FOS00 Function selector digital standard output OSD00 BRK_1 OPTN2 OPTN2 OPTN2
OSD01 241-FOS01 Function selector digital standard output OSD01 REF OPTN2 OPTN2 OPTN2
OSD02 242-FOS02 Function selector digital standard output OSD02 S_RDY OPTN2
Reference structure
280-RSSL1 Reference selector 1 FMAX FOPT2 FOPT2 FOPT2
281-RSSL2 Reference selector 2 FCON
289-SADD1 Offset for reference selector 1 10 0 0 0
Control location
260-CLSEL Control location selector TERM OPTN2 OPTN2 OPTN2
1) After setting the parameters of the user data sets, change parameter value 166-UDSSL from PARAM (KEYPAD KP200,
D
RIVEMANAGER) to TERM (terminal operation).
Table 4.22 Automatic changes by means of the assistance parameter
An empty line means that the setting is the same as for DRV_1 (factory 
setting).