6-18
Application Manual CDA3000
6 Control modes
6.1.4 _76 CI-Current
injection
CIFMx Limit frequency of current injection
CICNx Reference for current injection
MP Remagnetization
II Current injection
Figure 6.9 Current injection (II)
Parameters of current injection
Function Effect
Current injection via current
control as from a parameter-
izable limit value as a per-
centage of device rated
current
Increase the starting torque
up to the set limit frequency
t [s]
0
0
1
f [Hz]
v [m/s]
Start
I [A]
0
MP
II
CICNx
CIFMx
Parameter Function Value range FS Unit Online
760-CICN1 CDS1: Current injection reference 0 ... 180 120 %
761-CIFM1 CDS1: Current injection limit frequency 0 ... 100 4 Hz
762-CIFR1 CDS1: Current injection transition range 0.5 ... 10 2 Hz
763-CICN2 CDS2: Current injection reference 0 ... 180 120 %
764-CIFM2 CDS2: Current injection limit frequency 0 ... 100 4 Hz
765-CIFR2 CDS2: Current injection transition range 0.5 ... 10 2 Hz
766-CITM1 CDS1: Current injection timer for
switchover to CICT1
0 ... 60 6 s
Table 6.7 Parameters from subject area _76CI Current injection