Application Manual CDA3000
5-49
5  Software functions
1
2
3
4
5
6
A
DE
EN
FR
5.2.7 _26 CL-Control 
location
(1) Chosen control location
Figure 5.17 Function block: Control location selector
Parameters for control location
Settings of the control location selector 260-CLSEL
Function Effect
• The control location deter-
mines the source from which
the control commands are
given.
• Auto-Start after power-up
• Possible control locations
are:
-Terminals
-K
EYPAD KP200 control unit
- Serial interface
- Option slot 1 or 2
• Drive starts directly in Auto-
Start function if contact
ENPO is set.
Parameter Function Value range FS Unit Online
7-AUTO Auto-Start OFF/ON OFF
260 -CLSEL Control location selector see Table 5.28 TERM
Table 5.27 Parameters from subject area _26CL Control location
BUS KP/DM Function
0 TERM Terminals
1 KPAD KEYPAD KP200
2 SIO Serial interface RS232 (Serial Input Output)
3 OPTN1 Option module at slot 1 (user modules)
4 OPTN2 Option module at slot 2 (communication modules)
Table 5.28 Settings for 260-CLSEL Control location selector
(1)
CLSEL
OPTN2
OPTN1
SIO
KPAD
TERM