2-18
Application Manual CDA3000
2 Inverter module CDA3000
2.7 Reset Parameter reset
In PARA menu of KEYPAD: Press the two cursor keys to reset the para-
meter currently being edited to the factory defaults (152-ASTER =
DRV_1).
In D
RIVEMANAGER: In the edit window of the parameter editor choose the
Default button.
Factory setting of a data set
By setting parameter 4-PROG = 1 in subject area _86SY- System, the
active data set in the RAM is reset to its factory defaults.
Attention: The factory setting causes application data set 1 (traction and
lifting drive, DRV_1) to be loaded. Pay attention to the termi-
nal assignment and the functionality of the inverter module in
this operation mode.
Lastly, the factory setting in the RAM should be stored by way of parame-
ter 164-UMWR in subject area _15 FC-Initial commissioning in a user
data set. Caution: Storing the factory setting by way of 150-SAVE =
START in subject area _15 FC-Initial commissioning will result in user
data set 1 being overwritten, because it is preset by default in the factory
setting.
Factory setting of all user data sets
(complete device in delivery condition)
DRIVEMANAGER: By setting parameter 4-PROG = 850 in subject area
_86SY-System, the device is reset completely to its factory setting.
This includes all user data sets. During this process communication
with the D
RIVEMANAGER is cut. Reconnect.
K
EYPAD: You can achieve the same effect by simultaneously press-
ing the two cursor keys on the K
EYPAD KP200whiletheinverter
module is powering up. The K
EYPAD displays RESET.
The reset takes approx. 30 seconds to restore the factory defaults of all
user data sets. Then the device is ready to start again. User data set 1 is
in the active data set (RAM).