5-84
Application Manual CDA3000
5 Software functions
Status word 120-WRN
Warning Function Hex value Bit
WOTI
Warning message when heat sink tempera-
ture has exceeded value in parameter 500-
WLTI
0001H 0
WOTD
Warning message when interior tempera-
ture has exceeded value in parameter 501-
WLTD
0002H 1
WOTM
Warning message when motor temperature
has exceeded value in parameter 502-
WLTM
0004H 2
WOV
Warning message when DC-link voltage has
exceeded value in parameter 504-WLOV
0008H 3
WUV
Warning message when DC-link voltage has
fallen below value in parameter 503-WLUV
0010H 4
WFOUT
Warning message when output frequency
has exceeded value in parameter 505-WLF
0020H 5
WIS
Warning message when apparent current
has exceeded value in parameter 506-WLIS
0040H 6
WIIT
Warning message when I
2
*t integrator of
device is active
0080H 7
WFDIG
Warning message from slave when refe-
rence value from master is faulty in Master/-
Slave operation
0100H 8
WIT
Warning message when Ixt integrator of
motor is active
0200H 9
Table 5.48 Hexadecimal representation of warning messages