Application Manual CDA3000
5-87
5 Software functions
1
2
3
4
5
6
A
DE
EN
FR
Settings for 140-RNM to 534-R-LSW
531-EFSCL Ground fault detection response threshold
scaling
0 ... 200 0 %
532-R-PF Response after DC-link buffering STOP ... RESET STOP
533-R-FDG Response to reference coupling transmis-
sion error
STOP ... RESET STOP
534-R-LSW Response to reversed limit switches 1 ... 3 LOCK
543-R-OL5
from SW 2.0
Response to Ixt shut-off below 5 Hz
Stop ... Reset LOCK
94-TERR System time on occurrence of last error 0 ... 65535 0 h
95-ERR1 Last error 0 ... 65535 0 h
96-ERR2 Second-last error 0 ... 65535 0 h
97-ERR3 Third-last error 0 ... 65535 0 h
98-ERR4 Fourth-last error 0 ... 65535 0 h
Parameter Function Value range FS Unit Online
Table 5.50 Parameters from subject area _51ER Error messages
BUS KP/ DM Function
0 WRN No response
1 STOP Disable power stage
2LOCK
Disable power stage and secure against restarting
(prevent autostart)
3 RESET
Disable power stage and reset device after confirmation of error.
The device is rebooted and runs through an initialization and self-test
phase.
Table 5.51 Response to error