Application Manual CDA3000
5-131
5  Software functions
1
2
3
4
5
6
A
DE
EN
FR
Permissible rated current of three-phase inverter modules
0.75 kW to 90 kW
3 x 400 V  mains voltage
45 °C ambient temperature
4 kHz clock frequency
10 m motor cable
40 °C ambient temperature
8 kHz clock frequency
10 m motor cable
40 °C ambient temperature
16 kHz clock frequency
10 m motor cable
45 °C ambient temperature
4 kHz clock frequency
25 m motor cable
40 °C ambient temperature
8 kHz clock frequency
25 m motor cable
40 °C ambient temperature
16 kHz clock frequency
25 m motor cable
 Inverter modules
Rated current
[A] 
Rated current
[A] 
Rated current
[A] 
Rated current
[A] 
Rated current
[A] 
Rated current
[A] 
CDA34.003,Cx.x
2.2 2.2 1.8 2.0 1.7 0.5
CDA34.005,Cx.x
4.1 4.2 2.2 3.9 3.6 1.4
CDA34.006,Wx.x
5.7 5.7 3.2 5.5 5.2 2.6
CDA34.008,Wx.x
7.8 7.8
Not available 
at time of going to press
7.6 7.3
Not available 
at time of going to press
CDA34.010,Wx.x 10 10 9.8 9.5
CDA34.014,Wx.x
14 14 14 14
CDA34.017,Wx.x
17 17 17 17
CDA34.024,Wx.x
24 24 24 24
CDA34.032,Wx.x
32 32 32 32
CDA34.045,Wx.x
45 45 * 45 45 *
CDA34.060,Wx.x
60 60 * 60 60 *
CDA34.072,Wx.x
72 72 * 72 72 *
CDA34.090,Wx.x
90 90 * 90 90 *
CDA34.110,Wx.x
110 110 * 110 110 *
CDA34.143,Wx.x
143 143 * 143 143 *
CDA34.170,Wx.x
170 170 * 170 170 *
*  Not permitted
Table 5.86 Output current for inverter modules with 400 V power supply