6-46
Application Manual CDA3000
6 Control modes
Tips and optimization aids
Problem Cause Remedy
Implausibly high d-current
reference in motors with high
power output
The influence of the fault voltages at high
inverter outputs (typically > 22 kW) and
motors with low stator resistance results in
the magnetizing inductance being identified
too low.
Reduce switching frequency 690-PMFS to
4 kHz during auto-tuning.
Incorrect number of pole pairs
detected
Enter synchronous speed as nominal speed
or motor with large number of pole pairs
(p>4) and high slip frequency.
Correct rated speed of ASM:
Check rating plate data
Consult motor manufacturer or
Estimate a logical value
and then restart a new auto-tuning process
Enter correct number of pole pairs.
Torque too low because
operating point wrong
Imprecise data on motor rating plate.
Check plausibility of rating plate data.
Rated speed not attainable
because operating point wrong
Imprecise data on motor rating plate.
Check plausibility of rating plate data.
Table 6.22 Optimization aids