7 DIGITAL OSCILLOSCOPE
7.7 Digital Oscilloscope Status
7.7 Digital Oscilloscope Status
The digital oscilloscope status can be checked at the digital oscilloscope monitor.
Digital oscilloscope monitor data
■Bit device
■Word device
*1 Elapsed time (seconds) up to the current time using Greenwich Mean Time 00:00:00, January 1st 1970 as the reference can be
checked.
Monitor item Stored content Monitor value Refresh cycle Device No.
Sampling settings RUN
status
Turns ON when sampling is started.
Turns OFF when saving of the sampling results is
complete.
OFF: STOP
ON: RUN
When sampling
status changes (main
cycle)
SM760
Sampling settings trigger
status
Turns ON when trigger conditions are established.
Remains ON even when sampling is complete, and turns
OFF when starting sampling.
OFF: Before trigger
ON: After trigger
When trigger ON
(sampling cycle)
SM761
Sampling settings saving Turns ON while saving data in the buffer data to the storage
target when performing sampling.
OFF: Not while saving
ON: While saving
When file save status
changes (main cycle)
SM762
Monitor item Stored content Monitor value Refresh cycle Device No.
Sampling settings storage
target
The storage target for the sampling settings file being
sampled is stored.
0: No sampling
1: Standard ROM
2: SD memory card
When starting
sampling (main
cycle)
SD760
Sample settings results save
target
The sampling results save destination for the data being
sampled is stored.
0: No sampling
1: Standard ROM
2: SD memory card
SD761
Sampling settings
sampling type
The sampling type being sampled is stored. 0: No sampling
1: Trigger sampling
SD762
Sampling settings
sampling results
Latest file information
The latest sampling results file information (system time
*1
)
is stored.
Latest saved file
information
When outputting
sampling results
(main cycle)
SD764,
SD765