3 DEVICES
3.8 Latch Function
87
3
Clearing the latch range
The latch (1) and latch (2) ranges are cleared with the following operations. (Page 352 Memory Initialization)
Precautions
When increasing the ranges set for latch (1) or latch (2), the latch device value when the Multiple CPU system power
supply is turned ON again after parameter writing will be the value when the power supply was previously turned OFF.
All latch ranges are cleared if the device point setting, or device assignment method differs from the setting at the previous
operation when turning ON the Multiple CPU system or when resetting.
Latch range Clear operation
Latch (1) Clearing the MT Developer Motion CPU memory.
Cleaning built-in memory with Motion CPU rotary switch "C".
Latch (2) Cleaning built-in memory with Motion CPU rotary switch "C".

Table of Contents