289
APPENDICES
APPEN
DIX
Appendix 1 Parameter Setting
Appendix 1.2 PLC Parameter
(3) PLC File Setting
Parameters required for the files used in the CPU module are set.
Item
Parameter
No.
Description Setting range Default Reference
File Register
1100
H
Set a file for the file register used in the
program.
• Not used
• Use the following file
Use the following
file
Page 259,
Section 5.6
Transfer to Standard
ROM at Latch data
backup operation
1104
H
Select whether to batch-transfer the
data in the file register at the time of
latch data backup to the standard ROM.
Selected/deselected ⎯
Page 159,
Section 3.27
Comment File Used in a
Command
1101
H
Set a file for device comments used in
the program.
• Not used
• Use the same file name as
the program
• Use the following file
Not used ⎯
Initial Device Value
1102
H
Set a file for initial values of the devices
used for the CPU module.
• Not used
• Use the same file name as
the program
• Use the following file
Not used
Page 85,
Section 3.5
File for Local Device
1103
H
Set a file for local devices used in the
program.
• Not used
• Use the following file
Not used
Page 278,
Section 7.2
File used for SP.DEVST/
S.DEVLD Instruction
1105
H
Set a device data storage file used for
writing to or reading from the standard
ROM.
• Not used
• Use the following file
Not used
Page 164,
Section 3.28