EasyManua.ls Logo

MLC LC100 - Page 62

MLC LC100
148 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
62
LC100 Instruction manual
Messages that describe the contactor activation failure in the control group:
Screen message
ID
Description
52
Indicates a direction up contactor activation fault. Contactor is controled by
defined input FI-220. Contactor must be on 2 seconds after system turns on
the output function FO-001.
53
Indicates a direction down contactor activation fault. Contactor is controled
by defined input FI-221. Contactor must be on 2 seconds after system turns
on the output function FO-002.
54
Indicates a high speed contactor activation fault. Contactor is controled by
defined input FI-223. Contactor must be on 2 seconds after system turns on
the output function FO-004.
55
Indicates a low speed contactor activation fault. Contactor is controled by
defined input FI-222. Contactor must be on 2 seconds after system turns on
the output function FO-003.
56
Indicates motor contactors activation fault, used with frequency regulated
elevators . Contactors are controled by defined input FI-225.
57
Indicates a failure to activate electromechanical elevator brake. Brake
control is done over brake contact at the input FI-224. Signal must be present
while traveling, and max 2 seconds after direction contactors activation.
58
Indicates a frequency regulator fault. Controled by input FI-226. Regularity
signal must be present all time.
59
Indicates a „star“ contactor activation fault used with hydraulic elevators.
Contactor is controled by defined input FI-227. Contactor must be on 2
seconds after sytem turns on the output function FO-013.
60
Indicates a „delta“ contactor activation fault used with hydraulic elevators.
Contactor is controled by defined input FI-228
61
Indicates a motor fan contactor fault. Contactor is controled by defined input
FI-209. Contactor must be on after system turns on output function FO-018.
62
Indicates a phase presence and sequence control relay fault. Relay is
controled by input FI-204.
Table with warnings and other failures:
Screen message
ID
Description
29
Indicates that Bucher I-Valve don’t give output and it’s in error FI-313.
63
Indicates that the resistance of PTC sensor is above limit set by parameter
I-02 (hot state PTC resistance). Error remains on for another five min after
the signal, or once the probe resistnace falls below the value set by
parameter I-01 (cold state PTC resistance). Current PTC resistance can be
monitored in the menu inputs/outputs.
64
Indicates that the elevator after establishment of control signals from the
control group was not initiated in time set by parameter I-03. As a start
control, group takes into account all the signals except for a pulses for
copying used in copiying type 4 or 5 E-01. Parameter should be set to a
sufficient value needed to elevator pass the path between the 2 copiyng
signals when traveling at low speed increased by approximately 20%. After
activating the error it is necessary to reset the control disconnecting power
supply or using the reset button on LC100-D terminal. Inspection travel is
possible.
65
Indicates that the elevator after start from the station has not moved for
logner that the time set by parameter I-03. This message is identical to the
protection Start failure with the difference that after the start at least one
copying signal has changed . It is necessary to reset the control
disconnecting power supply or using the reset button on LC100-D terminal.

Table of Contents