Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-54
Moeller 07/01 AWB-C2700-1347GB
Moeller PS40
PLC Type Protocol PLC Port Parameter
PS4-141
PS4-151
PS4-201
PS4-341
SUCOM-A PRG 9600 baud, 8 data bits , 1 start bit, 1 stop bit,
no parity
DRIVER DESIGNATION ALT : PS4-141-MM1 > PRG (PS40.BIN)
DRIVER DESIGNATION ALT : PS4-151-MM1 > PRG (PS40.BIN)
DRIVER DESIGNATION ALT : PS4-201-MM1 > PRG (PS40.BIN)
DRIVER DESIGNATION ALT : PS4-341-MM1 > PRG (PS40.BIN)
SUPPORTED DATA TYPES : M, MB, MW, (MD for PS4-341-MM1)
WIRING LIST
RS 232
Signal Pin Pin Signal
RxD 2 5 TxD
TxD 3 2 RxD
SG 5 3 SG
ZB4-601/609-IF1 PS4-XXX
(9 pole male)
(5 pole DIN male)
Type: ZB4-237-KB1
NOTES
• The SUCOM-A protocol of the programming device is used when connecting the ZB4-601/609-IF1 to the
PRG interface.
This is part of the OS of the PLC and active communication must be possible directly afterwards.
• The ZB4-601/609-IF1 card must be set to “ALT” and the current PS40 driver (PS40.BIN) must be loaded
(for this see also sections 3.1).
• The PLC must be in “RUN” status for active communication.
• The data exchange is only carried out with the physical markers of the PLC.
• The following messages can be generated:
Suconet 1.00 CONNECT PLC not switched on or cable break
Suconet 1.00 ADDRESS Marker address outside of permissible range
Suconet 1.00 PLCRUN Master PLC not in “RUN”
Suconet 1.00 TIMEOUT Cycle time > 2.5 seconds
Suconet 1.00 PROTOCOL General protocol error
Suconet 1.00 READY Active data exchange