EasyManuals Logo

Motion Control Engineering Nidec iControl User Manual

Default Icon
453 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #58 background imageLoading...
Page #58 background image
2-35
Drive Offsets Calibration
iControl AC
2
2. Follow the on-screen instructions, “To perform the drive offsets calibration...” (cali-
brates Input ADC and Output DAC offset).
3. Once calibration is Done, the offset values shown on the Setup > Drive tab should match
those shown on the Drive Configuration tab (Configuration > Drive > Calibration tab).
Manual Drive Setup Procedure
MCE recommends first performing the Automated Drive Setup Procedure previously described
and then verifying the most critical offsets (Output DAC and Input ADC - Tachometer)
using the manual procedure. If the automated procedure is unsuccessful, the manual procedure
must be used.
Before adjusting the drive, verify that:
the CONTROLLER STOP switch is in the RUN position
the iBox Safety OK LED is ON
the iBox Door Locked LED is ON
the iBox Fault LED is OFF
iView is connected, write privilege has been obtained (Write Privilege > Acquire
selected and “Yes” softkey on iBox pressed in response)
1. Verify Pattern scaling is set to 100% (Configuration > Pattern > Common tab).
2. On iView, display the Drive - Offsets tab (Configuration > Drive > Calibration tab).
3. Output DAC: With zero speed commanded (car idle):
TORQMAX F5: verify that pattern voltage applied to the AC drive unit reads 0.0 volts
between F5 drive terminals X2A-1 (+) and X2A-2 (—).
Magnetek: verify that the D1 Speed Command value is zero). If not, adjust Output DAC
on the Drive/Calibration screen by entering and sending small negative or positive val-
ues until the reading is as close to 0.0 volts as possible (less than 1mV). The DAC
adjustment range is from —0.25 to +0.25 units.
4. On iView, display the Drive - Offsets tab (Configuration > Drive > Calibration tab). Also
display the Virtual Oscilloscope (View > Virtual Oscilloscope) and set Test point 1 =
Tachometer Signal.
5. Input ADC - Tachometer: Adjust the
Input ADC - Tachometer parameter by
entering and sending small negative or
positive values until the Test point 1
value is as close to 0.0 as possible
(20mV). The ADC adjustment range is
from —0.5 to +0.5.
6. Input ADC - Brake current: Set Virtual Oscilloscope Test Point 1 = Brake Current Feed-
back and adjust the Input ADC - Brake current parameter by entering and sending small
negative or positive values until the Test point 1 value is as close to 0.0 as possible.
7. Input ADC - Brake voltage: Set Virtual Oscilloscope Test Point 1 = Brake Voltage Feed-
back and adjust the Input ADC - Brake voltage parameter by entering and sending small
negative or positive values until the Test point 1 value is as close to 0.0 as possible.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Motion Control Engineering Nidec iControl and is the answer not in the manual?

Motion Control Engineering Nidec iControl Specifications

General IconGeneral
BrandMotion Control Engineering
ModelNidec iControl
CategoryControl Unit
LanguageEnglish

Related product manuals