EasyManua.ls Logo

Motorola GTR 8000 - General Battery Installation Recommendations; General Breaker Recommendations; Table 3-2 Heavy Gauge Wire Resistance Examples

Motorola GTR 8000
346 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GTR8000BaseRadio
AllACpowerequipmentandelectricalcomponentsmustconformtoNationalElectricalManufacturers
Association(NEMA)andNationalElectricalCode(NEC).ThesemustalsobelistedbyanNRTL.
Asurgearrestor,designedtoprotectequipmentsystemsfroma120/240Vserviceandloadcenter,isplaced
onthepowerfeedaheadofallindividualloadcentercircuitbreakers.Thisgaplessarrestormustbelisted
byanNRTLforthepurposeintended.
Selectionofasurgearrestorisbasedonthesusceptibilityoftheequipmentpoweredbytheelectricalservice,
withmarginprovidedforlocallygenerateddisturbances.SeeANSI/IEEEC62.41(21)formoredetails.
Atleastone120VAC,15Aduplexconvenienceoutletequippedwithgroundfaultinterrupter(GFI)
protectionmustbeprovidedintheelectronicequipmentcompartment.
Donotusesurge/transientsuppressorswithoutcarefulandexpertpowersystemanalysis.
SUGGESTION
RedundantdevicescouldbeterminatedondifferentACmainphasessothatasinglephasefailuredoesnot
resultinapowerlossforbothdevices.
3.3.8.2GeneralBreakerRecommendations
Inordertoensurethatafaultwhichcausesthebreakertoopendoesnotresultinthelossofmultipletransmit
channels,eachbaseradiopowersupplyshouldhaveitsownsupplybreaker.ThebreakerrecommendationsforAC
andDCsupplybreakersareasfollows:
Fora120V AC,60Hzapplication,theACsupplybreakershouldberatedforacontinuouscurrentof
20A.Fora220V AC,50Hzapplication,theACsupplybreakershouldberatedforacontinuouscurrent
of10Aminimum,nottoexceed20A.
IndividualDCbreakersarenotused.ForinformationinvolvingthesizingofcablesandDCpower
distribution,seetheStandardsandGuidelinesforCommunicationSitesmanual.
SiteinstallationshallincludeasinglecurrentinterruptingdeviceontheDCinputdistribution(fuseorcircuit
breaker)ratedfortheapplicationloading,nottoexceed200A.Foreachstandalonebaseradio,theDCsupply
breakershouldberatedforacontinuouscurrentof25A.
3.3.8.3GeneralBatteryInstallationRecommendations
Thebatteriesandchargershouldbeascloseaspossibletotherectiersystemusingthecables.Aheavygaugestrandedcable
isadvisedtominimizevoltagedrop.Examplesoftheresistanceofsomeheavygaugewireis:
Table3-2HeavyGaugeWireResistanceExamples
Gauge
Resistance
#6gauge
0.3951/1000ft
#4gauge
0.2485/1000ft
#2gauge
0.1563/1000ft
Themaximumvoltagedropcanbecalculatedbyknowingthepeakcurrentdrawnbytheradiosystem.Usethe
followingformula:
3-126871022P86-A-November2012

Table of Contents