EasyManuals Logo

Omron EJ1 User Manual

Omron EJ1
253 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #111 background imageLoading...
Page #111 background image
90
Detecting Current Errors Section 4-5
Examples
1. Single-phase Heaters
Example 1 Using a 200-VAC, 1-kW Heater
The heater current is 5 A when the current is normal, and 0 A when there is a
burnout, so the heater burnout detection current is calculated as follows:
Example 2 Using Three 200-VAC, 1-kW Heaters
The heater current is 15 A when the current is normal, and 10 A when there is
a burnout, so the heater burnout detection current is calculated as follows:
Heater burnout detection current =
Normal current value + Burnout current value
2
Normal operation Heater burnout occurred
CT
To CT input
AC line
Load
5 A
5 A
200 V
CT
To CT input
AC line
Load
0 A
200 V
Burnout
=
5 + 0
= 2.5 A
2
Normal operation Heater burnout occurred
CT
To CT input
AC line
Load
15 A
200 V Load Load
15 A
CT
To CT input
AC line
Load
10 A
200 V
Load Load
10 A
Burnout
Heater burnout detection current =
Normal current value + Burnout current value
2
=
15 + 10
= 12.5 A
2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron EJ1 and is the answer not in the manual?

Omron EJ1 Specifications

General IconGeneral
BrandOmron
ModelEJ1
CategoryTemperature Controller
LanguageEnglish

Related product manuals