160
Detailed Description of Services
Section 6-4
• LSP Mode and RSP Mode
Sets SP Mode (LSP (local SP)/RSP (remote SP).
An operation error will occur if autotuning is already being performed for a
specified channel.
• Reset Error
Clears the following errors: heater burnout latch, HS alarm latch, heater
overcurrent latch, heater overcurrent, and operation during error (selec-
tion B).
• Latch Cancel
Cancels alarm latches. This command is enabled when the alarm latch
function is used.
• Save RAM Data
Writes the settings for parameters that can be changed during operation
to EEPROM.
• Parameter Initialization
Returns the current set values to their default values. The setting is not
saved to EEPROM, however, so Save RAM Data 2 should be executed if
required.
Execute Save RAM Data 2 only when control operations are stopped for
all channels.
• Save RAM Data 2
Writes settings (except read-only settings) to EEPROM.
Execute Save RAM Data 2 only when control operations are stopped for
all channels.
• Register Unit Configuration
Registers or resets the G3ZA Unit Configuration. Refer to 4-7-4 Using
G3ZA Multi-channel Power Controllers for details on Unit configuration
registration.
Execute Save RAM Data 2 only when control operations are stopped for
all channels.
2. Response Codes
Response code Error name Cause
1001 Command too long The command is too long.
1002 Command too short The command is not long enough.
1100 Parameter error Bit position is not 00.
0402 Operation error
(0402)
The command cannot be executed because
the model or version is not the same.
2201 Operation error
(2201)
The command cannot be executed because
operation is stopped.
2202 Operation error
(2202)
The command cannot be executed during
operation.
2203 Operation error
(2203)
• The command cannot be executed in nor-
mal mode.
• The command cannot be executed in man-
ufacturer mode.
7011 Operation error
(7011)
The command cannot be executed due to a
device error.
7012 Operation error
(7012)
The command cannot be executed due to a
configuration error.
7013 Operation error
(7013)
The command cannot be executed because
the operation command cannot be received.
Execute retries until the 7013 response code