18
Wiring Terminals Section 2-2
EDU
2-2-2 Wiring Precautions
Separate input leads and power lines to protect the EJ1 from external
noise.
Use AWG22 (cross-sectional area: 0.326 mm
2
) to AWG14 (cross-sec-
tional area: 2.081 mm
2
) twisted-pair cable for power supply and AWG28
(cross-sectional area: 0.081 mm
2
) to AWG16 (cross-sectional area:
1.309 mm
2
) for all other cables. The stripping length is 6 to 8 mm.
Use crimp terminals when wiring the terminals.
Tighten the terminal screws to a torque of 0.40 to 0.56 N·m.
Up to two wires of the same size and same type or two crimp terminals
can be inserted into a single terminal.
Use the following types of crimp terminals for M3 screws.
RS-485
RS-485
1
2
3
4
5
6
7
8
9
Port A connector
SUB2
SUB1
Port B
24 VDC
B (+)
A ()
COM
Port A
B (+)
A ()
These two ports cannot be
used at the same time.
These terminals cannot be
used when an HFU is used.
Input power supply
+
5.8 mm max.
5.8 mm max.