EasyManuals Logo

Omron MX2 Series User Manual

Omron MX2 Series
612 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #193 background imageLoading...
Page #193 background image
4 Parameter List
4 - 33
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Monitor or data range
Default
data
Set
data
Changes
during
RUN
Unit
Page
Control
parameters
H030
1st Motor Parameter
R1
(Auto-tuning Data)
0.001 to 65.535
Depen-
dent on
capacity
Disabled
P. 6-4
H230
2nd Motor Parameter
R1
(Auto-tuning Data)
Depen-
dent on
capacity
Disabled
H031
1st Motor Parameter
R2
(Auto-tuning Data)
0.001 to 65.535
Depen-
dent on
capacity
Disabled
H231
2nd Motor Parameter
R2
(Auto-tuning Data)
Depen-
dent on
capacity
Disabled
H032
1st Motor Parameter L
(Auto-tuning Data)
0.01 to 655.35
Depen-
dent on
capacity
Disabled
mH
P. 6-4
H232
2nd Motor Parameter
L
(Auto-tuning Data)
Depen-
dent on
capacity
Disabled
H033
1st Motor Parameter
Io
(Auto-tuning Data)
0.01 to 655.35
Depen-
dent on
capacity
Disabled
A
H233
2nd Motor Parameter
Io
(Auto-tuning Data)
Depen-
dent on
capacity
Disabled
H034
1st Motor Parameter J
(Auto-tuning Data)
0.001 to 9999.000
*1
Depen-
dent on
capacity
Disabled
kgm
2
H234
2nd Motor Parameter
J
(Auto-tuning Data)
Depen-
dent on
capacity
Disabled
H050
V/f Control With
Speed Feedback Slip
Compensation
Proportional Gain
0.00 to 10.00
0.20
Enabled
time
P. 6-24
H051
V/f Control With
Speed Feedback Slip
Compensation
Integral Gain
0. to 1000.
2.
Enabled
s
H102
PM Motor Parameter
Selection
00: Standard PM motor parameter
01: Auto-tuning parameter
00
Disabled
P. 6-62
H103
PM Motor Capacity
0.1/0.2/0.4/0.55/0.75/1.1/1.5/2.2/3.0/3.7/
4.0/5.5/7.5/11.0/15.0/18.5
Maximum
applica-
ble motor
capacity
Disabled
kW
H104
PM Motor Pole
Number
2/4/6/8
10 to 488: Do not set.
Depen-
dent on
capacity
Disabled
pole
H105
PM Motor Rated
Current
0.00 to 1.00 Rated current
Depen-
dent on
capacity
Disabled
A
H106
PM Motor
Parameter R
0.001 to 65.535
Depen-
dent on
capacity
Disabled
H107
PM motor
Parameter Ld
0.01 to 655.35
Depen-
dent on
capacity
Disabled
mH
H108
PM motor
Parameter Lq
0.01 to 655.35
Depen-
dent on
capacity
Disabled
mH
4
4-3 Extended Function Mode
4-3-4 Group H: Motor Control Parameters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron MX2 Series and is the answer not in the manual?

Omron MX2 Series Specifications

General IconGeneral
Cooling MethodFan cooling
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, Sensorless vector control
Protection FunctionsOvercurrent, overvoltage, undervoltage, overload, overheating, short circuit
Communication OptionsModbus RTU
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Ambient Operating Temperature-10°C to +50°C
EnclosureIP20
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Power Supply Voltage200-240V AC
Input Voltage3-phase 200-240V AC

Related product manuals