Electronic thermal detection of the inverter
The electronic thermal function for the inverter is fixed to the rated current value of the inverter, inde-
pendent of the b012/b212 setting.
However, the characteristics of the Inverter change because the rated current of the Inverter varies
with the normal and light load mode settings.
Below are the electronic thermal characteristics of the inverter.
Basic Characteristics in Heavy load Mode Basic Characteristics in Light Load Mode
Overload detection time [s] Overload detection time [s]
Precautions for Correct Use
The inverter will trip if an overload is detected by either the inverter or motor electronic thermal
function.
The motor electronic thermal function detects E05., and the inverter thermal function detects
E38..