Precautions for Correct Use
•
The reset function clears the data of calculated electronic thermal function and calculated
usage rate of regenerative braking.
Therefore, frequent use of the reset function causes the motor overload protection and brak-
ing resistor overheat protection functions of the inverter to malfunction.
If you execute the reset function continuously, wait until the motor and braking resistor tem-
peratures drop.
To shut off the inverter output, use the free-run stop function, instead of the reset function.
•
When a trip occurs, the inverter will ignore the RUN command even if it is ON.
Enter the RUN command again after inputting the reset signal.