7 Other Functions
7 - 64
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Data
Default
data
Unit
b003
Restart Standby Time
0.3 to 100.0
Set the wait time until the inverter restarts.
1.0
s
b007
Frequency Pull-in Lower
Limit Frequency
0.00 to 590.00
Executing the function causes the Inverter to
restart from 0 Hz if the frequency at shutoff is
the set value of b007 or less.
0.00
Hz
b028
Frequency Pull-in Restart
Level
0.20 Rated current to 2.00 Rated current
Rated
current of
inverter
A
b029
Frequency Pull-in Restart
Parameter
0.1 to 3000.0
Set the deceleration rate for the output fre-
quency during frequency pull-in restart.
Set the deceleration time from the maximum
frequency to 0 Hz.
0.5
s
b030
Starting Frequency Selec-
tion at Frequency Pull-in
Restart
00: Frequency at shutoff
01: Maximum frequency
02: Set frequency (Frequency reference)
00
7
7-7 Restart Functions
7-7-1 Frequency Pull-in Restart

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron MX2 Series and is the answer not in the manual?

Omron MX2 Series Specifications

General IconGeneral
Cooling MethodFan cooling
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, Sensorless vector control
Protection FunctionsOvercurrent, overvoltage, undervoltage, overload, overheating, short circuit
Communication OptionsModbus RTU
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Ambient Operating Temperature-10°C to +50°C
EnclosureIP20
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Power Supply Voltage200-240V AC
Input Voltage3-phase 200-240V AC

Related product manuals