7 Other Functions
7 - 64
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Data
Default
data
Unit
b003
Restart Standby Time
0.3 to 100.0
Set the wait time until the inverter restarts.
1.0
s
b007
Frequency Pull-in Lower
Limit Frequency
0.00 to 590.00
Executing the function causes the Inverter to
restart from 0 Hz if the frequency at shutoff is
the set value of b007 or less.
0.00
Hz
b028
Frequency Pull-in Restart
Level
0.20 Rated current to 2.00 Rated current
Rated
current of
inverter
A
b029
Frequency Pull-in Restart
Parameter
0.1 to 3000.0
Set the deceleration rate for the output fre-
quency during frequency pull-in restart.
Set the deceleration time from the maximum
frequency to 0 Hz.
0.5
s
b030
Starting Frequency Selec-
tion at Frequency Pull-in
Restart
00: Frequency at shutoff
01: Maximum frequency
02: Set frequency (Frequency reference)
00
7
7-7 Restart Functions
7-7-1 Frequency Pull-in Restart