7 Other Functions
7 - 102
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Function
Value
Remarks
STO response time
20 ms
Time from transition of the GS1 and GS2
signals to the STO status until shutoff of the
power to the motor
EDM response time
30 ms
Time from transition of the GS1 and GS2
signals to the STO status until EDM signal
ON
Parameter
Value
Standard
PL
e
EN ISO 13849-1: 2015
CAT.
3
MTTFd
100years
DCavg
>99%
SIL
3
IEC61508: 2010
IEC61800-5-2: 2016
EN61800-5-2: 2017
HFT
1
SFF
>90%
PFH
<2×10
-8
PFD
<2×10
-4
TM
10years
Response Time
7
7-10 Safety Function