7 Other Functions
7 - 102
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Function
Value
Remarks
STO response time
20 ms
Time from transition of the GS1 and GS2
signals to the STO status until shutoff of the
power to the motor
EDM response time
30 ms
Time from transition of the GS1 and GS2
signals to the STO status until EDM signal
ON
Parameter
Value
Standard
PL
e
EN ISO 13849-1: 2015
CAT.
3
MTTFd
100years
DCavg
>99%
SIL
3
IEC61508: 2010
IEC61800-5-2: 2016
EN61800-5-2: 2017
HFT
1
SFF
>90%
PFH
<2×10
-8
PFD
<2×10
-4
TM
10years
Response Time
7
7-10 Safety Function
7-10-1 Overview of Safety Function
Parameters Related to Safety

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron MX2 Series and is the answer not in the manual?

Omron MX2 Series Specifications

General IconGeneral
Cooling MethodFan cooling
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, Sensorless vector control
Protection FunctionsOvercurrent, overvoltage, undervoltage, overload, overheating, short circuit
Communication OptionsModbus RTU
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Ambient Operating Temperature-10°C to +50°C
EnclosureIP20
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Power Supply Voltage200-240V AC
Input Voltage3-phase 200-240V AC