Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Phase-to-phase sinusoidal modulation PWM
Digital command: 0.01% of the maximum frequency, Analog command:
0.2% of the maximum frequency (2510°C)
Frequency setting
resolution
Digital setting: 0.01 Hz, Analog setting: Maximum frequency 1/1000
Voltage/Frequency
characteristics
V/f characteristics (constant torque, reduced torque)
Sensorless vector control, V/f control with speed feedback
Overload current rating
of inverter
Heavy load rating (CT): 150%/60 s
Light load rating (VT): 120%/60 s
Instantaneous overcur-
rent protection
200% of heavy load rating (CT) value
Acceleration/
Deceleration time
0.00 to 3600 s (line/curve arbitrary setting), 2nd acceleration/deceleration
setting provided
Carrier frequency
change range
2 to 15 kHz (Derating required)
200%/0.5 Hz (Sensorless vector control)
Operates at operating frequency or less during deceleration via STOP
command, at set frequency or less during operation, or via external input
(level and time can be set).
Overcurrent, Overvoltage, Undervoltage, Electronic thermal, Tempera-
ture error, Ground-fault current at power-on, Inrush current protection cir-
cuit, Overload limit, Incoming overvoltage, External trip, Memory error,
CPU error, USP error, Communication error, Overvoltage suppression
during deceleration, Power interruption protection, Emergency shutoff,
Analog current input (New), STO internal fault (New), etc.
Digital Operator
External analog input signal (variable resistor/0 to 10 VDC/4 to 20 mA),
Modbus communication
Digital Operator
External digital input signal (3-wire input available), Modbus communica-
tion
7 points (Functions can be selected from among 66)
2 points (O terminal for voltage: 10 bits/0 to 10 V, OI terminal for current:
10 bits/4 to 20 mA)
2 points (32 kHz max., EA terminal: 5 to 24 VDC, 7 terminal: 24 VDC)
2 points (GS1,GS2: Dedicated terminals)
2 points (11 and 12 terminals: Functions can be selected from among
47)
1 point (SPDT contact (AL0, AL1, AL2), Functions can be selected from
among 47)
Analog output
(Frequency monitor)
*5
1 point (AM terminal: 10 bits for voltage, 0 to 10 V) (Frequency or current
can be selected)
1 point (EO terminal: 32 kHz max., 0 to 10 V)
RJ45 connector (for Digital Operator)
Control circuit terminal, Modbus communication
USB2.0, Micro-B connector
1-3-1 Standard Specifications