8 Communications Functions
8 - 27
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Register
No.
Modbus
register
spec.
No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolu-
tion
1F34 hex
1F33 hex
1st Multi-step Speed
Reference 0
A020
R/W
0/Starting Frequency to 1st
Maximum Frequency
0.01
[Hz]
1F35 hex
1F34 hex
Multi-step Speed
Reference 1
A021
R/W
0/Starting frequency to
Maximum frequency
0.01
[Hz]
1F36 hex
1F35 hex
Multi-step Speed
Reference 2
A022
R/W
0/Starting frequency to
Maximum frequency
0.01
[Hz]
1F37 hex
1F36 hex
Multi-step Speed
Reference 3
A023
R/W
0/Starting frequency to
Maximum frequency
0.01
[Hz]
1F38 hex
1F37 hex
1st Frequency Upper Limit
A061
R/W
0/Frequency Lower Limit to
Maximum Frequency
0.01
[Hz]
1F39 hex
1F38 hex
1st Frequency Lower Limit
A062
R/W
0 to Frequency Upper Limit
0.01
[Hz]
1F3A hex
1F39 hex
Acceleration Stop Fre-
quency
A069
R/W
0.00 to Starting Frequency:
Disabled
Frequency above Starting
Frequency to 59000
0.01
[Hz]
1F3B hex
1F3A hex
Frequency Addition
Amount Setting
A145
R/W
0 to 59000
0.01
[Hz]
1F3C hex
1F3B hex
Deceleration Stop Fre-
quency
A154
R/W
0.00 to Starting Frequency:
Disabled
Frequency above Starting
Frequency to 59000
0.01
[Hz]
1F3D hex
1F3C hex
PID Sleep Operation
Level
A156
R/W
0 to 59000
0.01
[Hz]
1F3E hex
1F3D hex
Frequency Pull-in Lower
Limit Frequency
b007
R/W
0 to 59000
0.01
[Hz]
8-7 Modbus Mapping Function
8-7-3 Compressed Single-word Registers
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Name
In7
In6
In5
In4
In3
In2
In1
RS
EXT
Dir
Opr

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron MX2 Series and is the answer not in the manual?

Omron MX2 Series Specifications

General IconGeneral
Cooling MethodFan cooling
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, Sensorless vector control
Protection FunctionsOvercurrent, overvoltage, undervoltage, overload, overheating, short circuit
Communication OptionsModbus RTU
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Ambient Operating Temperature-10°C to +50°C
EnclosureIP20
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Power Supply Voltage200-240V AC
Input Voltage3-phase 200-240V AC