EasyManuals Logo

Omron MX2 Series User Manual

Omron MX2 Series
612 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #483 background imageLoading...
Page #483 background image
8 Communications Functions
8 - 39
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Coil No.
Modbus coil
spec. No.
Item
R/W
Description
002E hex
002D hex
ODc (Analog O
disconnection detection)
R
1: ON
0: OFF
002F hex
002E hex
OIDc (Analog OI
disconnection detection)
R
1: ON
0: OFF
0030 hex
Reserved
0031 hex
0032 hex
0031 hex
FBV (PID feedback
comparison)
R
1: ON
0: OFF
0033 hex
0032 hex
NDc (Communications
disconnection detection)
R
1: ON
0: OFF
0034 hex
0033 hex
LOG1 (Logic operation output
1)
R
1: ON
0: OFF
0035 hex
0034 hex
LOG2 (Logic operation output
2)
R
1: ON
0: OFF
0036 hex
0035 hex
LOG3 (Logic operation output
3)
R
1: ON
0: OFF
0037 to
0039 hex
Reserved
003A hex
0039 hex
WAC (Capacitor life warning)
R
1: ON
0: OFF
003B hex
003A hex
WAF (Cooling fan life
warning)
R
1: ON
0: OFF
003C hex
003B hex
FR (Starting contact signal)
R
1: ON
0: OFF
003D hex
003C hex
OHF (Cooling fin overheat
warning)
R
1: ON
0: OFF
003E hex
003D hex
LOC (Low current signal)
R
1: ON
0: OFF
003F to
0044 hex
Reserved
0045 hex
0044 hex
IRDY (Operation ready)
R
1: ON
0: OFF
0046 hex
0045 hex
FWR (Forward run signal)
R
1: ON
0: OFF
0047 hex
0046 hex
RVR (Reverse run signal)
R
1: ON
0: OFF
0048 hex
0047 hex
MJA (Fatal fault signal)
R
1: ON
0: OFF
0049 hex
0048 hex
During data write
R
1: Writing
0: Normal
004A hex
0049 hex
CRC error
*1
R
1: Error
0: No error
004B hex
004A hex
Overrun error
*1
R
1: Error
0: No error
004C hex
004B hex
Framing error
*1
R
1: Error
0: No error
004D hex
004C hex
Parity error
*1
R
1: Error
0: No error
004E hex
004D hex
Checksum error
*1
R
1: Error
0: No error
8
8-9 Modbus Communication Data Lists
8-9-1 Coil Number List

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron MX2 Series and is the answer not in the manual?

Omron MX2 Series Specifications

General IconGeneral
Cooling MethodFan cooling
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, Sensorless vector control
Protection FunctionsOvercurrent, overvoltage, undervoltage, overload, overheating, short circuit
Communication OptionsModbus RTU
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Ambient Operating Temperature-10°C to +50°C
EnclosureIP20
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Power Supply Voltage200-240V AC
Input Voltage3-phase 200-240V AC