EasyManua.ls Logo

Omron MX2 Series

Omron MX2 Series
612 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Communications Functions
8 - 44
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Register
No.
Modbus
register
spec.
No
Function name
Parameter No.
R/W
Monitor or setting
data
Data
resolution
003A
hex
0039 hex
Fault Monitor 5 Fault
Factor
d085
R
Refer to Inverter trip
fault factor list on
page 8-46.
003B
hex
003A hex
Fault Monitor 5 Inverter
Status
Refer to Inverter trip
fault factor list on
page 8-46.
003C
hex
003B hex
Fault Monitor 5 Frequency
(HIGH)
0 to 59000
0.01
[Hz]
003D
hex
003C hex
Fault Monitor 5 Frequency
(LOW)
003E
hex
003D hex
Fault Monitor 5 Output
Current
Output current
value at the time of
trip
0.01 [A]
003F
hex
003E hex
Fault Monitor 5 Main circuit
DC voltage
DC input voltage at
the time of trip
0.1 [V]
0040
hex
003F hex
Fault Monitor 5 Total RUN
Time (HIGH)
Total RUN time
before the trip
1 [h]
0041
hex
0040 hex
Fault Monitor 5 Total RUN
Time (LOW)
0042
hex
0041 hex
Fault Monitor 5 Total
Power ON Time (HIGH)
Total power ON
time before the trip
1 [h]
0043
hex
0042 hex
Fault Monitor 5 Total
Power ON Time (LOW)
0044
hex
0043 hex
Fault Monitor 6 Fault
Factor
d086
R
Refer to Inverter trip
fault factor list on
page 8-46.
0045
hex
0044 hex
Fault Monitor 6 Inverter
Status
Refer to Inverter trip
fault factor list on
page 8-46.
0046
hex
0045 hex
Fault Monitor 6 Frequency
(HIGH)
0 to 59000
0.01
[Hz]
0047
hex
0046 hex
Fault Monitor 6 Frequency
(LOW)
0048
hex
0047 hex
Fault Monitor 6 Output
Current
Output current
value at the time of
trip
0.01 [A]
0049
hex
0048 hex
Fault Monitor 6 Main circuit
DC voltage
DC input voltage at
the time of trip
0.1 [V]
004A
hex
0049 hex
Fault Monitor 6 Total RUN
Time (HIGH)
Total RUN time
before the trip
1 [h]
004B
hex
004A hex
Fault Monitor 6 Total RUN
Time (LOW)
004C
hex
004B hex
Fault Monitor 6 Total
Power ON Time (HIGH)
Total power ON
time before the trip
1 [h]
004D
hex
004C hex
Fault Monitor 6 Total
Power ON Time (LOW)
004E
hex
004D hex
Warning Monitor
d090
R
Warning code
004F to
08FF
hex
Not used
Not accessible

Table of Contents