8 Communications Functions
8 - 63
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
1320
hex
131F hex
Soft Lock Selection
b031
R/W
00: Data other than
b031 cannot be
changed when ter-
minal SFT is ON.
01: Data other than
b031 and the set
frequency cannot
be changed when
terminal SFT is ON.
02: Data other than
b031 cannot be
changed.
03: Data other than
b031 and set fre-
quency cannot be
changed.
P. 7-54
1321
hex
Reserved
1322
hex
1321 hex
Motor Cable Length
b033
R/W
5 to 20
1 [m]
1323
hex
1322 hex
RUN Time/Power
ON Time Detection
Level
b034
(HIGH)
R/W
0 to 65535
10 [h]
P. 7-84
1324
hex
1323 hex
b034
(LOW)
R/W
1325
hex
1324 hex
RUN Direction Limit
Selection
b035
R/W
00: No direction limit
01: Only Forward is
enabled (Reverse
is limited)
02: Only Reverse is
enabled (Forward
is limited)
P. 7-38
1326
hex
1325 hex
Reduced Voltage
Startup Selection
b036
R/W
0 (Reduced voltage
startup time: Short) to
255 (Reduced voltage
startup time: Long)
P. 7-36
1327
hex
1326 hex
Display Selection
b037
R/W
00: Complete display
01: Individual display
of functions
02: User setting
+d001, F001, b037
03: Data comparison
display
05: Monitor display
only + b037
P. 5-3
8
8-9 Modbus Communication Data Lists
8-9-4 Group A/b/C/H/P Register List