8 Communications Functions
8 - 67
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
135C
hex
135B hex
Automatic Carrier
Reduction
b089
R/W
00: Disabled
01: Enabled (depen-
dent on current)
02: Enabled (depen-
dent on cooling fin
temperature)
P. 7-32
135D
hex
135C hex
Usage Rate of
Regenerative
Braking
b090
R/W
0: Regenerative brak-
ing not active
1 to 1000 (limited by set-
ting in b097.)
0.1 [%]
P. 5-64
135E
hex
135D hex
Stop Selection
b091
R/W
00: Deceleration stop
01: Free-run stop
P. 5-38
135F
hex
135E hex
Cooling Fan
Operation
b092
R/W
00: Always enabled
01: Enabled only
during operation
(including 3 min-
utes after power-on
and 3 minutes after
Inverter operation
stop)
02: Dependent on
cooling fin tem-
perature
P. 7-86
1360
hex
135F hex
Total Fan Operation
Time Clear
b093
R/W
00: Clear disabled
01: Executes Clear
(Resets to 00 after
execution.)
1361
hex
1360 hex
Initialization Target
Setting
b094
R/W
00: All data
01: Data other than
terminals/commu-
nications
02: U*** registration
function only
03: Other than U***
registration func-
tion and b37
P. 5-5
1362
hex
1361 hex
Regenerative
Braking Selection
b095
R/W
00: Disabled (Function
not active)
01: Enabled (Disabled
during stop)
02: Enabled (Enabled
during stop)
P. 5-64
1363
hex
1362 hex
Regenerative Brak-
ing ON Level
b096
R/W
200-V class:
330
to
400
400-V class:
660
to
800
1 [V]
P. 5-64
8
8-9 Modbus Communication Data Lists
8-9-4 Group A/b/C/H/P Register List