11 Maintenance and Inspection
11 - 8
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Inspection
category
Inspection
item
Inspection
point
Inspection
frequency
Inspection method
Criteria
Meter
Daily
Periodic
1 year
2 years
Main
circuit
Inverter
unit
Converter
unit
(including
resistors)
Check resis-
tance between
terminals.

Disconnect wires from
the inverter main circuit
terminal block and mea-
sure the resistance
between the terminals
R/L1, S/L2, T/L3 and the
terminals P/+2, N/, and
between the terminals
U/T1, V/T2, W/T3 and the
terminals P/+2, N/ with a
tester in the 1 range.
Refer to 11-1-7
Inverter/Converter
Unit Test on page
11-10.
Inverter unit replace-
ment interval:
10
6
start-stop
cycles
*3
Analog
tester
Smoothing
capacitor
*1
Check that there
is no liquid leak-
age.
Perform visual inspec-
tion.
No faults
Capacity
meter
Check that the
safety valve
does not come
out and that
there is no
bulge.
Relay
Check for chat-
tering sound
during opera-
tion.

Perform acoustic inspec-
tion.
No faults
Check for rough
contact surface.

Perform visual inspec-
tion.
No faults
Control
circuit,
protection
circuit
Operation
check
Check output
voltage balance
between phases
during
stand-alone
inverter opera-
tion.

Measure the line voltage
between the inverter
main circuit terminals
U/T1, V/T2, and W/T3.
Phase-to-phase volt-
age balance
200-V class:
4 V max.
400-V class:
8 V max.
Digital
multimeter
Rectifier
Voltmeter
Check that there
is no error in
protection and
display circuits
through
sequence pro-
tection function
test.

Short-circuit or open the
inverter protection circuit
output under simulated
conditions.
Error is found in the
sequence.
Cooling
system
Cooling
fan
Check for
abnormal vibra-
tion and sound.
Rotate the fan manually
with the power off.
Smooth rotation, no
faults
*2
Check for loose
connections.

Perform visual inspec-
tion.
Cooling
fin
Check for clog-
ging.

Perform visual inspec-
tion.
No clogging

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron MX2 Series and is the answer not in the manual?

Omron MX2 Series Specifications

General IconGeneral
Cooling MethodFan cooling
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, Sensorless vector control
Protection FunctionsOvercurrent, overvoltage, undervoltage, overload, overheating, short circuit
Communication OptionsModbus RTU
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Ambient Operating Temperature-10°C to +50°C
EnclosureIP20
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Power Supply Voltage200-240V AC
Input Voltage3-phase 200-240V AC