Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
The limitation on the braking power and carrier frequency for DC injection braking is changed as
follows. Refer to 7-9-1 DC Injection Braking (DB) on page 7-93 for information on the DC injection
braking.
The DC injection braking power is limited according to
the carrier frequency setting.
100
90
80
(75)
Limit value
70
for DC
60
injection
50
(46)
braking
40
power
(34)
(%)
30
(22)
20
10
(10)
0 3
5
7 9 11 13 15
DC injection braking carrier frequency (kHz)
The carrier frequency is automatically reduced
according to the braking power.
15
12
11
Carrier
9
frequency
(kHz)
7
5
(5)
3
(2)
2
0
10 20 30 40 50 60 70 80 90 100
Braking power (%)
1
1
1
1
1
Limit value
1
for carrier
frequency
(kHz)
1
0
10
20
30
40
50
60
70
80
90
100
DC injection braking power (%)
: Relationship between DC injection braking power and
limit value for carrier frequency (3G3MX2-EV2 Series)
: Relationship between DC injection braking power and
limit value for carrier frequency (3G3MX2-E Series)
: Cannot be set for 3G3MX2-EV2 Series
(Carrier frequency is automatically reduced)
Relationship between DC Injection Braking Power and Carrier
Frequency
1-5 Comparison with Previous
Model
1-3-2 External Dimensions