4-72
Note
Related page
•Aparameterisdesignatedasfollows:
•ForparameterswhichNo.haveasuffixof“
*
”,changedcontentswillbevalidatedwhen
youturnonthecontrolpower.
•P.3-32...“InputsandoutputsonconnectorX4”
Default: [ ]
Pr6.22
*
A,Bphaseexternalscalepulseoutput
method selection
Range Unit Default
Related
control mode
0 to 1 — 0 F
SelectthepulseregenerationmethodofA,BandZparallelexternalscale.
Setup value Regenerating method
[0] DirectlyoutputthesignalsfromA,BandZparallelexternalscales.
1
OutputAandBphasesignalsrecoveredfromA,BandZparallelexternalscales.
Z-phase is output directly.
Pr6.23
Load fluctuation compensating gain
Range Unit Default
Related
control mode
−100to100 % 0 P S F
Setsthecompensationgainfortheloaductuation.
Pr6.24
Load fluctuation compensating filter
Range Unit Default
Related
control mode
10 to 2500 0.01 ms 53 P S F
Setstheltertimeconstantfortheloaductuation.
Pr6.27
*
Alarm latch time selection
Range Unit Default
Related
control mode
0 to 10 — 5 P S T F
Set up the latch time.
Setup value Content
0 Latchtime:innite
1
Latch time
1 [s]
2 2 [s]
3 3 [s]
4 4 [s]
[5] 5 [s]
6 6 [s]
7 7 [s]
8 8 [s]
9 9 [s]
10 10 [s]
Pr6.28
*
Special function selection
Range Unit Default
Related
control mode
0 to 1 — 0 P
Selectsbetweenenablinganddisablingtheblockoperationfunction.
Setup value Writing
[0] Block operation disabled
1 Block operation enabled
1. Details of parameter
[Class 6] Special setting